NeotechNeotech World- Managing Process Better
http://www.neotechworld.com
contents
 
Search this site
Quick Links:
Industrial Oil Filteration Plants and Cleaners at Neotech
Microcare EOC
Transformer Oil Filteration
 
   
Transformer Oil Filteration & Dehydration Plants Available With Neotech: (contd..2)
TRANSFORMER OIL FILTRATION & DEHYDRATION PLANTS(SINGLE STAGE):

These plants are designed for filtration and Dehydration of Power and distribution Transformers and oil in Tank. These plants can also be used for hot oil circulation in transformers and Transformer drying. These plants are available SERIES S(Stationery units),Series P (units in castors) & Series M(units in trailer)

TECHNICAL SPECIFICATIONS
Technical Specifications
1-V-060
1-V-120
1-V-240
1-V-450
1-V-600
Flow Rate - LPH
600
1200
2400
4500
600
Heater Capacity-K.W
6
18
45
63
81
Single Stage Rotary Oil Sealed Vacuum Pump
100 LPM
300 LPM
500 LPM
1000 LPM
2000 LPM
Total Power Required
7.5 K.W
20 K.W
50 K.W
70 K.W
96 K.W
Fine Filter Elements Moulded Cellulose
2
4
9
18
27
Filter Fineness
3/0.5 mu
Dimensions in metres
Stationery Unit,W/L/H
0.6/0.9/1.4
0.8/1.2/1.5
1/1.8/1.6
1.2/2.0/1.7
1.2/2.4/1.8
Unit on Castors,W/L/H
0.6/0.9/1.6
0.8/1.2/1.7
1.0/1.8/1.9
1.2/2.0/2.0
1.2/2.4/2.1
Unit on Trailer,W/L/H
1.2/1.4/2.1
1.4/1.7/2.2
1.6/2.2/2.4
1.8/2.4/2.6
1.8/2.8/2.6
Max. Oil Content in Transformer-Ltrs
1000
2500
7500
20000
35000

The plant will be mobile type moounted on castor wheels.It will also be suitable for conditioning of hydraulic and turbine oil.It will also remove suspended impurities colloidal carbon,dust,rust,scales etc. It will also remove moisture,volatile matters.It will mainly consist of following components:

* Oil Transfer & Circulation System:The plants will have two pumps for oil transfer & circulation.Both pumps will be positive displacement gear type,directly coupled with electric motor.The plant will have necessary valves & piping to ensure easy operation & maintenance.

* Heating System:The plant will have an insulated heater chamber with indirect type bobbin heaters for heating of oil upto 80 degree centigrades, how ever the working temperature for filtration will be 55 degree centigrade.Heater pipes will be finned to have more efficient heat transfer.Temperature will be controlled with thermostat or TIC.

* Filtration System:The plant will have 3 stage filtration system.In Pre-filter coarse particles along with magnetic particles.Intermidiate filter will be provided to increase the life of fine filter & it will remove particles upto 100 microns.Fine Filter will remove all solid impurities like coloidal carbon,oxidation sludge,dust/burr.It will be easily replaceable.Compound gauge will be provided to indicate the dirt accumulation in fine filter.Fine filter will also act as dispersing media in degassing chamber.

* Degassing Chamber & Vacuum System :The oil dispersed while passing through fine filter will be sprayed on raschig ring tray to have an exposure of oil film to vacuum,beacause of which moisture removal rate will be increased.Degassing chamber will be evacuated with rotary oil sealed vacuum pump,moisture trap,valves etc.

* The plants will have centralized CONTROL PANEL,Gauges & instruments to ensure easy & fool proof operation of the plant.

* OPTIONAL FEATURES: Transformer Evacuation System,Ionoc Reaction Column,Spirafuge(for coarse seperation), etc. can be provided on request.

* THESE PLANTS ARE SUITABLE FOR HYDRAULIC OIL, TURBINE OIL, THERMIC FLUID, etc.

TRANSFORMER OIL FILTRATION & DEHYDRATION PLANTS(TWO STAGE):

These plants work on high Vacuum and are designed for Filtration & Dehydration especially of Power Transformer at site.

TECHNICAL SPECIFICATIONS
Technical Specifications
2-V-060
2-V-120
2-V-240
2-V-450
2-V-600
Flow Rate - LPH
600
1200
2400
4500
600
Heater Capacity-K.W
9
27
54
81
108
Roots pump backed by Two Stage Rotary Oil Sealed Vacuum Pump
60 M3/Hr
100 M3/Hr
200 M3/Hr
400 M3/Hr
550 M3/Hr
Total Power Required
10.5 K.W
29 K.W
60 K.W
87 K.W
115 K.W
Fine Filter Elements Moulded Cellulose
2
4
9
18
27
Filter Fineness
3/0.5 micron
Dimensions in metres
Stationery Unit,W/L/H
0.6/0.9/1.4
1.0/1.6/2.0
1/2.1/2.0
1.2/2.5/2.0
1.2/2.6/2.2
Unit on Castors,W/L/H
0.6/0.9/1.6
1.0/1.6/2.2
1.0/2.1/2.2
1.2/2.5/2.2
1.2/2.6/2.6
Unit on Trailer,W/L/H
1.2/1.4/2.1
1.0/1.6/2.6
1.0/2.1/2.6
1.8/2.5/2.8
1.8/2.8/3.0
Max. Oil Content in Transformer-Ltrs
1000
2500
10000
25000
50000

All Above models are available in stationery version with model name
S-2V-120,S-2V-240,S-2V-450,S-2V-600.
Back to Top 
Powered by:
        
Your Information Powerhouse  © Copyright 2001 Neotech Equipments Private Limited. All rights reserved.
Send mail to Webmaster with questions or comments about this web site.